NC vs. NO Refrigerant Solenoid Valves: How to Select the Right Configuration for Refrigeration Systems

China Ningbo Brando Hardware Co., Ltd certification
China Ningbo Brando Hardware Co., Ltd certification
Nice supplier, fast speed response, fast delivery time, high quality product. I am lucky to find you!

—— John Smith

Delay to write down comments upon received goods one week ago. The solenoid valve working well on our equipment, thank you a lot, friend!

—— Leo Nirva

Service is very good, BRANDO company is nice company!

—— Bob Steve

Helped me made out difficult product and also the quality is very well, I will place you my new order soon.

—— Wellni Frankly

I'm Online Chat Now
Company News
NC vs. NO Refrigerant Solenoid Valves: How to Select the Right Configuration for Refrigeration Systems
Latest company news about NC vs. NO Refrigerant Solenoid Valves: How to Select the Right Configuration for Refrigeration Systems
NC vs. NO Refrigerant Solenoid Valves: How to Select the Right Configuration for Refrigeration Systems
Understanding Normally Closed and Normally Open Refrigerant Solenoid Valves

Refrigerant solenoid valves play an important role in controlling refrigerant flow in refrigeration and HVAC systems. For OEM manufacturers, system designers, and refrigeration equipment buyers, selecting the correct valve involves more than checking connection sizes and pressure ratings. One of the first considerations is the valve's normal position: Normally Closed (NC) or Normally Open (NO).

These two configurations have different operating principles and are designed for different control requirements. The FDF and FDF-K series provide examples of both configurations.

1. Normally Closed (NC) Solenoid Valves

A Normally Closed solenoid valve remains closed when its coil is de-energized. When electrical power is applied, electromagnetic force actuates the valve and opens the refrigerant flow path. When power is removed, the valve returns to its closed position.

This configuration is suitable for systems where the refrigerant circuit is required to remain closed in the de-energized state.

The FDF Series is designed as a Normally Closed refrigerant solenoid valve. According to its product specifications, the series includes direct-acting and pilot-operated configurations, depending on the model.

Its product introduction specifies a maximum working pressure of 3.4 MPa. Different orifice sizes are available to accommodate different refrigeration system requirements.

2. Normally Open (NO) Solenoid Valves

A Normally Open solenoid valve operates in the opposite way. It remains open when the coil is de-energized and closes when electrical power is applied.

The FDF-K Series features a Normally Open, direct-acting design. Its FDF2AK model has a 2.0 mm orifice and a 6.35 mm (1/4-inch) connection outside diameter.

The product documentation specifies a maximum working pressure of 1.5 MPa. This configuration should be evaluated according to the equipment's control sequence and required refrigerant flow condition when power is unavailable.

3. Five Key Factors in Refrigerant Solenoid Valve Selection
1. Normal Position: NC or NO

Determine whether the refrigerant circuit needs to remain open or closed when the valve coil is de-energized. The decision should follow the system control logic rather than the valve's appearance or model name.

2. Operating Mechanism: Direct Acting or Pilot Operated

Direct-acting valves use electromagnetic force to actuate the valve mechanism directly. Pilot-operated designs use a pilot mechanism to control the main valve.

The FDF Series offers different actuation configurations, while the FDF-K Series documentation identifies its design as direct acting. Always verify the operating mechanism of the selected model.

3. Operating Pressure Differential (OPD)

Minimum and maximum operating pressure differentials are important selection parameters.

For example, the FDF2AK model specifies a minimum OPD of 0 bar and a maximum OPD of 34 bar. These values are useful when evaluating operating conditions, although the complete model specifications must still be checked before selection.

4. Orifice Size and Flow Capacity

The FDF Series offers orifice sizes ranging from 1.9 mm to 13 mm, with Kv values ranging from 0.08 to 3.5 m³/h across different models.

Engineers should consider refrigerant type, required flow capacity, and system operating conditions when selecting an orifice size. A larger orifice does not automatically mean better performance for every application.

5. Coil Voltage

The FDF Series supports several electrical configurations: 12VDC, 24VDC, 24VAC, 110VAC, and 220VAC.

The selected coil voltage must match the equipment's electrical control system. Coil specifications should also be checked for the exact model.

4. Choosing Between the FDF and FDF-K Series

For applications requiring the refrigerant flow path to remain closed when electrical power is removed, the FDF Normally Closed series can be evaluated.

For systems requiring an open valve position in the de-energized state, the FDF-K Normally Open series may be a suitable option, subject to operating conditions.

Before finalizing a selection, verify refrigerant compatibility, working pressure, operating pressure differential, orifice size, connection dimensions, and coil voltage. Series-level specifications should not replace individual model data.

5. Conclusion

The primary difference between NC and NO refrigerant solenoid valves is their default position when the coil is de-energized. The FDF and FDF-K series provide both configurations for different refrigerant flow control requirements in refrigeration and HVAC applications.

For OEM manufacturers and system designers, evaluating control logic, OPD, Kv, orifice size, and electrical ratings together provides a more appropriate basis for valve selection than comparing connection dimensions alone.