Check all power, air, and hydraulic sources
The 50% troubleshooting problem is basically a problem with power, air and hydraulic sources. For example, there is a problem with the power supply, including the fault of the entire workshop power supply, such as low power supply, burned out of the insurance, poor contact of the power plug, etc.; the air pump or hydraulic pump is not turned on, the pneumatic triple or the two-piece is not opened, and the relief valve in the hydraulic system Or some pressure valves are not open, etc. These basic problems are usually the most common ones.
Check sensor position for offset
Due to the negligence of equipment maintenance personnel, there may be errors in the position of some sensors, such as not in place, sensor failure, sensitivity failure, etc. Always check the sensor's sensing position and sensitivity, and adjust the deviation in time. If the sensor is broken, replace it immediately. Many times, if the power supply, air supply and hydraulic source are supplied without errors, more problems are the sensor failure. Especially for magnetic inductive sensors, due to long-term use, it is very likely that the internal grounding irons stick to each other, cannot be separated, and a normally closed signal appears, which is also a common problem of this type of sensor and can only be replaced. In addition, due to the vibration of the equipment, most of the sensors will have a loose position after long-term use. Therefore, during routine maintenance, always check whether the sensor is in the correct position and is firmly fixed.
Check relay, flow control valve, pressure control valve
Like the magnetic inductive sensor, the relay can also be stuck in the long-term use, so that the electrical circuit cannot be guaranteed to be normal and needs to be replaced. In pneumatic or hydraulic systems, the throttle opening and the pressure regulating spring of the pressure valve may also loosen or slide as the device vibrates. These devices, like sensors, are components in the device that require routine maintenance. Therefore, in daily work, these devices must be carefully checked.
Check electrical, pneumatic and hydraulic circuit connections
If no problems are found in the above three steps, then all circuits are checked. Check if there is any open circuit in the circuit, especially if the wire in the wire slot is broken by the wire slot. Inspect the air tube for damaging creases. Check if the hydraulic hose is clogged.
When checking the circuit at this step, use the necessary multimeter, adjust to the buzzer file, and check the path of the loop. If there is a serious crease in the trachea, replace it immediately and replace the hydraulic tubing.
Decade
Contact Person: Mr. Brandon Bao
Tel: 86-13454729544
Fax: 86-574-83879820
3'' DMF-Z-76S BFEC Diaphragm Pulse Jet Solenoid Valve For Bag Filter
CA25DD Goyen Type DD Series Pulse Jet Diaphragm Valve For Dust Collector
1'' SCG353A044 ASCO Type Diaphragm Pulse Jet Valve For Dust Removal
EVR 3 NC 032F8107 1/4'' Danfoss Type Refrigeration Solenoid Valve 220VAC
1028/3 Castel Type 3/8'' Refrigeration Solenoid Valve HM2 220VAC 230VAC
EVRA 40 EN-JS1025 Danfoss Type Ammonia Solenoid Valve 042H1128 042H1132
C113443 C113444 Diaphragm For ASCO Pulse Valve SCG353A043 SCG353A044
Diaphragm For BFEC Pulse Valve 1.5'' DMF-Z-40S DMF-ZM-40S DMF-Y-40S
K7600 K7601 Diaphragm Kit For Goyen Pulse Solenoid Valve CA76T CA76MM